GDRB-Ⅱ Sweep Frequency Response Analyzer
GDRB-Ⅱ Transformer Frequency Response Tester detects transformer winding movements and mechanical failures due to mechanical shock, transportation or short circuits. Detection of these displacements ahead of a dielectric failure can reduce unplanned maintenance costs, and provide the possibility to improve system reliability by preventing outages. Additionally, when damage is discovered, repairs may be targeted to a specific phase winding. GDRB-Ⅱ can detect all level power transformers.
Technical specifications
General
- Operating Temperature: -10 .. +60°C
- Storage Temperature: -20 .. +70°C
- Relative Humidity: 10 .. 90 % non-condensing
- Mains Universal: 220±10% (110±10%) VAC, 50 / 60 Hz, 100W
- Dimensions Instrument: 32cm x 30cm x 12 cm
- Weight Instrument: 20 kg
- Automatic interpretation according to Chinese standard DL/T911-2004.
Calibration interval: 3 years
Measurement
- Source output: one channel
- Source frequency range: 10Hz~10MHz
- Source Frequency accuracy: 0.01%
- Source impedance: 50Ω
- Source amplitude: Max.10Vpeak_peak,user difined
- Analog input number: two channels
- Input impedance: 50Ωor 1MΩ
- Sampling: Max 100MHz per channel
- Accuracy: 0.5dB at +20dB~-80dB
- Dynamic range: +20dB~-80dB
- Protection: against short circuit overload
Measuring Points: max. 3’000, user defined
Data Display and Data export
- Plot: Frequency vs. Magnitude, Impedance, Phase
- Sweep mode :Scaling Logarithmic or Linear